When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.
Official Consumer Product Safety Recall • March 31, 2016

Gamewell-FCI Recalls Fire Alarm Panels Due to Failure to Alert of a Fire, Smoke or CO

This recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected.

Required Consumer Action

Consumers should immediately contact the distributor to obtain the free repair, a firmware upgrade.

Contact Information

Gamewell-FCI at 800-274-4324 from 7 a.m. to 7 p.m. ET Monday through Friday or online at www.gamewell-fci.com and click on "Safety Recall" for more information.

Recall Details

Sold At
Authorized distributors from May 2015 through August 2015 for about $800.
Injuries
No incidents or injuries have been reported.
Remedy
Repair
Recall Number
16134

Product Information

Product Name
Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3)
Product Type
Fire or Smoke Alarms
Number of Units
About 1,000
Distributed By
Gamewell-FCI of Northford, Conn.
Manufactured In
United States

Register This Product

Contact Manufacturer

Use the contact information below to reach out about this recall:

Phone 800-274-4324
Full Contact Information

Gamewell-FCI at 800-274-4324 from 7 a.m. to 7 p.m. ET Monday through Friday or online at www.gamewell-fci.com and click on "Safety Recall" for more information.